Study Shows Value of Sensor-controlled, Bi-Level Lighting

February 8, 2019

Considerable energy savings can be achieved with sensor-controlled, bi-level corridor lighting, according to results of a field demonstration led by the Lighting Research Center (LRC) at Rensselaer Polytechnic Institute.

The field demonstration looked at sensor-controlled, bi-level corridor lighting in a multi-family apartment building. 

“Saving lighting energy in multi-family corridors is becoming more feasible,” says Jennifer Brons, who authored a report on the field demonstration. “LED luminaires can easily dim light output when corridors are vacant, rather than turning off entirely. Most importantly, the occupants had positive comments about safety and comfort with sensor-controlled, bi-level lighting.”

Dimming light output when corridors are vacant, rather than turning off entirely, is referred to as “bi-level” or “adaptive” lighting. Sensors can be mounted in each luminaire, or can be wirelessly linked to multiple luminaires. 

Project background

With support from the New York State Energy Research and Development Authority, the LRC and Taitem Engineering collaborated with Albany Housing Authority to upgrade 60 corridor lights on six floors of a below-market-rate apartment building in Albany, New York, known as Lincoln Square Two. Monitoring results from 14 other apartment buildings enabled energy savings calculations comparing market rate vs. below market rate buildings.

Lincoln Square Two is part of a complex of high-rise apartments built in the 1960s. The project involved upgrading 60 corridor lights (6 floors, 10 per floor). 

Previous lighting consisted of linear T8 fluorescent lamps4 in surface-mounted luminaires spaced typically 13 feet
(4 m) apart. Although lamps were in good working order, plastic cube louvers had yellowed with age, thus distorting colours and reducing luminaire light output. Before the retrofit, average illuminance on the floor was 106 lux (10 fc). 

For this research, each of the previous fluorescent luminaires were replaced one-for-one with LED luminaires controlled by integrated ultrasonic occupancy sensors. Luminaires were rotated to orient parallel to the corridor to improve light distribution on the walls. Each of the new luminaires was set to operate at 100% output when occupied (average 303 lux at floor level); when vacant, luminaires dimmed independently to 20% of full output. Twenty of the new luminaires were set for each of the three delay time settings: 5, 10, or 15 minutes.

Resident feedback

The LRC administered a questionnaire to compare occupant acceptance to the conventional, fixed-output fluorescent lighting in use before the retrofit. Despite the higher light levels with the new lighting, most occupants did not consider the hallways too bright after retrofit. Over three-quarters (78%) of the occupants approve of the new bi-level lighting. More of the occupants had positive ratings after retrofit than before retrofit.

The occupants also offered positive comments about the retrofit. Multiple people commented that they like how the individually controlled luminaires ramp up light output successively as they walk through the corridor. One person likes that the sensors act as a notification that others are present. Several people simply prefer having more light in the corridors, independent of sensor features. There were no negative comments about the sensors. 

Estimated annual energy use 

Energy impacts were studied for the three delay time settings. Luminaires programmed with the shortest sensor delay time (5 minutes) operated at high output for less time (22%) compared to those programmed with longer (15 minute) delay times (31%). This resulted in 14% less annual energy use for the short delay time setting compared to the long delay time setting. 

Proximity to elevator lobbies increased the amount of time luminaires were at high output, and therefore reduced energy savings in these areas. However, even in busy elevator lobbies, bi-level lighting used about half as much energy as only upgrading to fixed-output LEDs. 

The LRC calculated annual energy use for 48 luminaires comparing the previous T8 fluorescent luminaires to two conditions: LED luminaires without sensors, and bi-level lighting programmed with a 5-minute time delay. At this high-rise residential site, use of sensors to create bi-level lighting more than doubled energy savings compared to upgrading to fixed-output LEDs.

Key findings

The Lincoln Square bi-level lighting demonstration showed that

  • over three-quarters (78%) of the occupants approved of the new bi-level lighting
  • 5-minute delay time was not objectionable
  • dimming to 20% light output when vacant was not objectionable
  • use of sensors to create bi-level lighting more than doubled energy savings compared to upgrading to fixed-output LEDs
  • the lower the dim setting when vacant, the greater the energy savings due to bi-level lighting

Read the full study here.

Related Articles


Changing Scene


Design

  • Artika: Outdoor Wall Lighting Ideas – Security, Style & Curb Appeal

    Artika: Outdoor Wall Lighting Ideas – Security, Style & Curb Appeal

    Strategic outdoor wall lighting combines bright entry fixtures (700-1,000 lumens) at doors, accent sconces highlighting architectural features, and porch lighting that creates welcoming curb appeal while deterring intruders and ensuring safe navigation. Your home’s exterior walls offer the perfect canvas for lighting that serves multiple purposes simultaneously. Well-positioned outdoor wall lights provide security at vulnerable… Read More…

  • Mac’s II Agencies: Transform Your Space – 6 Ways to Light Corridors That Leave an Impression

    Mac’s II Agencies: Transform Your Space – 6 Ways to Light Corridors That Leave an Impression

    Corridors are transitional spaces that connect us from room to room, level to level, yet they’re often fitted with a series of basic downlights in the design process. But what if I told you that corridor lighting could be so much more? After a decade in the lighting industry, I’ve learned that lighting is one… Read More…


New Products

  • Dals: Horizon Max 100W Flood Light – DCP-FLD100

    Dals: Horizon Max 100W Flood Light – DCP-FLD100

    Dals Horizon Max is the big brother to their original Horizon, delivering significantly higher lumen output while maintaining the same build quality and adjustability. Constructed from high-strength aluminum alloy, the Horizon Max features a wide 120-degree beam angle and can be wall-mounted or staked in the ground. The wall plug can also be cut for… Read More…

  • BeLuce: HAZ-X A – Hazardous Location LED Flood Light

    BeLuce: HAZ-X A – Hazardous Location LED Flood Light

    The HAZ-X A Series LED Flood Light is an ideal choice for marine and hazardous applications. They can be used in locations where moisture, dirt, dust, corrosion and vibration may be present, or areas where wind, water, snow or high ambient temperatures can be expected. Available in configurations from 20W to 400W, the HAZ-X A… Read More…